Phoenix Air Systems PE-Series
Penthouse Refrigeration
PE Unit Construction includes:
- IMP type foamed panel construction of roof and walls
Up to 6" thick panels, with R-49 rating
Cam-lock design for vapor-tight panel-to-panel seal
Standard smooth galvanized interior finish
White embossed galvanized exterior finish
Optional stainless steel, aluminum and non-metallic surfaces available
- Full sized freezer doors for unit access
Flush-mount door with compressible gaskets
Double latch with interior/exterior release mechanism
Heated door jambs pre-wired to junction box
- Unit designed for installation on flat roof
- Galvanized steel construction of internal structure
- Walk-on gratings over return air opening and supply fans
- Standard 1200 RPM TEAO, EPAC efficiency motors
Fan motors pre-wired to a NEMA-4 junction box on the unit exterior
Motors include low temperature grease
- Aluminum prop fans for efficient operation
Adjustable fans used for light duty applications (coolers and low horsepower)
Rugged cast fans used for heavy duty applications (freezers and higher horsepower)
- Fan/motor service davit
- Units with hot gas pan coils are shipped with a full size hot gas check valve